Frequently Asked Questions | 1. | What is backflow?
| | 2. | What is cross-connection?
| | 3. | What is backpressure backflow?
| | 4. | What is backsiphonage?
| | 5. | Where did the need for backflow prevention originate?
| | 6. | What is a backflow preventer?
| | 7. | I have several backflow preventers (DCV, etc.). What do these mean?
| | 8. | Why should I test these devices every year?
|
| | 1. | What is backflow? | | | Backflow is the undesirable reversal of flow of nonpotable water or other substances through a cross-connection and into the public water system (potable water). There are two types of backflow - backpressure and backsiphonage. A backflow system is designed to protect the potable water from contamination, which could occur if the pressure exceeds potable water pressure over a cross-connection where one (or more) of the check valves fail. | | | Return to Top
| | 2. | What is cross-connection? | | | Any actual or potential connection between a drinking water supply and a possible source of contamination or pollution (eg, a wastewater line). | | | Return to Top
| | 3. | What is backpressure backflow? | | | Backpressure is backflow caused by a downstream pressure that is greater than the upstream or supply pressure in a public water system or consumer's potable water system. Backpressure (i.e., downstream pressure that is greater than the potable water supply pressure) can result from an increase in downstream pressure, a reduction in the potable water supply pressure, or a combination of both. Increases in downstream pressure can be created by pumps, temperature increases in boilers, etc. Reductions in potable water supply pressure occur whenever the amount of water being used exceeds the amount of water being supplied, such as during water line flushing, fire fighting, or breaks in water mains. | | | Return to Top
| | 4. | What is backsiphonage? | | | Backsiphonage is backflow caused by a negative pressure (i.e., a vacuum or partial vacuum) in a public water system or consumer's potable water system. The effect is similar to drinking water through a straw. Backsiphonage can occur when there is a stoppage of water supply due to nearby fire fighting, a break in a water main, etc. | | | Return to Top
| | 5. | Where did the need for backflow prevention originate? | | | Introduction to the Clean Water Act The Clean Water Act (CWA) is the cornerstone of surface water quality protection in the United States. (The Act does not deal directly with ground water nor with water quantity issues.) The statute employs a variety of regulatory and nonregulatory tools to sharply reduce direct pollutant discharges into waterways, finance municipal wastewater treatment facilities, and manage polluted runoff. These tools are employed to achieve the broader goal of restoring and maintaining the chemical, physical, and biological integrity of the nation's waters so that they can support "the protection and propagation of fish, shellfish, and wildlife and recreation in and on the water." For many years following the passage of CWA in 1972, EPA, states, and Indian tribes focused mainly on the chemical aspects of the "integrity" goal. During the last decade, however, more attention has been given to physical and biological integrity. Also, in the early decades of the Act's implementation, efforts focused on regulating discharges from traditional "point source" facilities, such as municipal sewage plants and industrial facilities, with little attention paid to runoff from streets, construction sites, farms, and other "wet-weather" sources. Starting in the late 1980s, efforts to address polluted runoff have increased significantly. For "nonpoint" runoff, voluntary programs, including cost-sharing with landowners are the key tool. For "wet weather point sources" like urban storm sewer systems and construction sites, a regulatory approach is being employed. Evolution of CWA programs over the last decade has also included something of a shift from a program-by-program, source-by-source, pollutant-by-pollutant approach to more holistic watershed-based strategies. Under the watershed approach equal emphasis is placed on protecting healthy waters and restoring impaired ones. A full array of issues are addressed, not just those subject to CWA regulatory authority. Involvement of stakeholder groups in the development and implementation of strategies for achieving and maintaining state water quality and other environmental goals is another hallmark of this approach. Source: www.epa.gov | | | Return to Top
| | 6. | What is a backflow preventer? | | | A backflow preventer is a means or mechanism to prevent backflow. The basic means of preventing backflow is an air gap, which either eliminates a cross-connection or provides a barrier to backflow. The basic mechanism for preventing backflow is a mechanical backflow preventer, which provides a physical barrier to backflow. The principal types of mechanical backflow preventer are the reduced-pressure principle assembly, the pressure vacuum breaker assembly, and the double check valve assembly. A secondary type of mechanical backflow preventer is the residential dual check valve. | | | Return to Top
| | 7. | I have several backflow preventers (DCV, etc.). What do these mean? | | | RP(RPZ): An RP (reduced principle assembly) is a mechanical backflow preventer that consists of two independently acting, spring-loaded check valves with a hydraulically operating, mechanically independent, spring-loaded pressure differential relief valve between the check valves and below the first check valve. It includes shutoff valves at each end of the assembly and is equipped with test cocks. An RP is effective against backpressure backflow and backsiphonage and may be used to isolate health or nonhealth hazards. PVB: A PVB (pressure vacuum breaker) assembly is a mechanical backflow preventer that consists of an independently acting, spring-loaded check valve and an independently acting, spring-loaded, air inlet on the discharge side of the check valve. It includes shutoff valves at each end of the assembly and is equipped with test cocks. A PVB may be used to isolate health or nonhealth hazards but is effective against backsiphonage only. DCV: A DCV (double check valve) assembly is a mechanical backflow preventer that consists of two independently acting, spring-loaded check valves. It includes shutoff valves at each end of the assembly and is equipped with test cocks. A DC is effective against backpressure backflow and backsiphonage but should be used to isolate only nonhealth hazards. | | | Return to Top
| | 8. | Why should I test these devices every year? | | | Mechanical backflow preventers have internal seals, springs, and moving parts that are subject to fouling, wear, or fatigue. Also, mechanical backflow preventers and air gaps can be bypassed. Therefore, all backflow preventers have to be tested periodically to ensure that they are functioning properly. A visual check of air gaps is sufficient, but mechanical backflow preventers have to be tested with properly calibrated gauge equipment. | | | Return to Top
|
|
|
|
|